Controllers
HI 700 and HI 710 Conductivity Controllers
Commonly used in boiler, cooling tower and
electroplating applications, conductivity is also used in brewery, food,
paper/textile and detergent manufacturing processes.
The "Technical Info" area of this website
discusses conductivity measurement in greater detail. (see blue underlined link
below)
Technical Article: Conductivity Measurement
Process controllers shown below are used
for all of the applications listed above.
Key Features:
- Dual setpoint with On-Off and PID
control output
- Outputs:
- Analog recorder output, 4-20mA,
0-5VDC, 0-10VDC
- Relay Control outputs: two @ 5A SPDT
- RS-485 output opto-isolated,
bi-directional (if analog output is not specified)
- Alarm relay, 5A SPDT
- Manual or automatic temperature
compensation (with Pt-100 RTD input)

- Password protection
- Conductivity input either: 4-20mA or
4-Ring probe
- Calibration: automatic or manual single
point
- Adjustable temperature coefficient
- Range: 0.0 to 200,000
μS/cm
- Dual scale version has
both μS/cm
units and TDS units ppm
- Temperature range of
input: -10ºC to 100ºC
- Accuracy: 0.5%
- Panel cutout: 5.5" x 5.5"
(140mm x140mm)
- Dimensions: 1/2 DIN
(144mm x144mm) x 6.7" (170mm)
- Optional: Wall mounted enclosure (HI 23)
- Weight: 3.5 lbs (1.6kg)
- Power: 115VAC or 230VAC
Probe, HI 7639:
The recommended sensor (HI 7639) for this controller
uses a four ring potentiometric method of measuring conductivity. The
rings are made of platinum and provides a more stable measurement over a wide
range. Unlike conventional sensors, this probe does not need frequent
calibration. And because of its design, polarization is not an issue.
The internal RTD provides the controller with automatic temperature
compensation.
- Sensor: 4-Ring Platinum
- Body: Ultem high temperature plastic and glass
- Connection: 3/8" NPT Stainless Steel threaded
- Cable: 4 meters
- Temperature compensation: Pt100
- Length: 60mm (not including threads)
- Diameter of sensor: 12 mm
- Maximum temperature: 120ºC
(248ºF)
- Maximum pressure: 5 bar (73 psi)
Transmitter, HI 8936:
Using a similar sensor (HI 7638) the
Hanna Conductivity Transmitter series allows a temperature compensated analog
signal to be input to the controller. The transmitters require 24vdc
external power to energize the loop current.
- Output: 4-20mA (maximum 500Ω)
- Enclosure: IP65 Waterproof
- Local display: Optional
- Temperature compensation: 0-50ºC
- Calibration: 2 point
- Ranges (selectable):
- 0.0-199.9mS/cm
- 0.00-19.99mS/cm
- 0-1999 ųS/cm
- 0.0-199.9 ųS/cm
|